⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 750 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.54V (11.28%)
Voltage at Load End117.3 VLoss: 2.74 V (1162.6 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 750 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1999.15 V (1665.96%)0.0 V3297.66 V (2748.05%)849639.2 WDrop/Amp High
12 AWG3.31 mm²20 A1256.26 V (1046.89%)0.0 V2072.25 V (1726.87%)533912.2 WDrop/Amp High
10 AWG5.26 mm²30 A790.54 V (658.78%)0.0 V1304.02 V (1086.68%)335979.0 WDrop/Amp High
8 AWG8.37 mm²50 A496.8 V (414.0%)0.0 V819.49 V (682.91%)211140.9 WDrop/Amp High
6 AWG13.3 mm²65 A312.65 V (260.54%)0.0 V515.73 V (429.77%)132875.9 WDrop/Amp High
4 AWG21.15 mm²85 A196.61 V (163.84%)0.0 V324.31 V (270.26%)83557.9 WDrop/Amp High
3 AWG26.67 mm²100 A155.91 V (129.93%)0.0 V257.19 V (214.32%)66263.6 WDrop/Amp High
2 AWG33.62 mm²115 A123.68 V (103.07%)0.0 V204.02 V (170.02%)52565.4 WDrop/Amp High
1 AWG42.41 mm²130 A98.05 V (81.71%)22.0 V161.73 V (134.78%)41670.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A77.74 V (64.78%)42.3 V128.23 V (106.86%)33038.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A61.67 V (51.39%)58.3 V101.72 V (84.77%)26208.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A48.91 V (40.76%)71.1 V80.69 V (67.24%)20788.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A38.79 V (32.32%)81.2 V63.98 V (53.32%)16485.5 WDrop/Amp High
250 kcmil126.7 mm²255 A32.82 V (27.35%)87.2 V54.14 V (45.11%)13948.3 WDrop/Amp High
300 kcmil152.0 mm²285 A27.36 V (22.8%)92.6 V45.13 V (37.6%)11626.6 WDrop/Amp High
350 kcmil177.3 mm²310 A23.45 V (19.54%)96.5 V38.69 V (32.24%)9967.6 WDrop/Amp High
400 kcmil202.7 mm²335 A20.51 V (17.1%)99.5 V33.84 V (28.2%)8718.5 WDrop/Amp High
500 kcmil253.4 mm²380 A16.41 V (13.67%)103.6 V27.07 V (22.56%)6974.1 WDrop/Amp High
600 kcmil304.0 mm²420 A13.68 V (11.4%)106.3 V22.56 V (18.8%)5813.3 WDrop/Amp High
750 kcmil380.0 mm²475 A10.94 V (9.12%)109.1 V18.05 V (15.04%)4650.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.21 V (6.84%)111.8 V13.54 V (11.28%)3487.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 750 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 750 feet one-way at 120V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.74V (2.28%) and delivers 117.3V at the load.

What size aluminum wire is required for 425 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.54V (11.28%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.