🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.19%
Aluminum Wire (≤3% Drop)4 AWGDrop: 10.9V (2.27%)
Voltage at Load End469.5 VLoss: 10.51 V (819.3 W)
Power & Breaker (125%)37.41 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A67.22 V (14.0%)412.8 V110.87 V (23.1%)5239.0 WDrop/Amp High
12 AWG3.31 mm²20 A42.24 V (8.8%)437.8 V69.67 V (14.52%)3292.2 WDrop/Amp High
10 AWG5.26 mm²30 A26.58 V (5.54%)453.4 V43.84 V (9.13%)2071.7 WDrop/Amp High
8 AWG8.37 mm²50 A16.7 V (3.48%)463.3 V27.55 V (5.74%)1301.9 W~ ≤5%
6 AWG13.3 mm²65 A10.51 V (2.19%)469.5 V17.34 V (3.61%)819.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A6.61 V (1.38%)473.4 V10.9 V (2.27%)515.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A5.24 V (1.09%)474.8 V8.65 V (1.8%)408.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.16 V (0.87%)475.8 V6.86 V (1.43%)324.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.3 V (0.69%)476.7 V5.44 V (1.13%)256.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.61 V (0.54%)477.4 V4.31 V (0.9%)203.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.07 V (0.43%)477.9 V3.42 V (0.71%)161.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.64 V (0.34%)478.4 V2.71 V (0.57%)128.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.3 V (0.27%)478.7 V2.15 V (0.45%)101.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.1 V (0.23%)478.9 V1.82 V (0.38%)86.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.92 V (0.19%)479.1 V1.52 V (0.32%)71.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.79 V (0.16%)479.2 V1.3 V (0.27%)61.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.69 V (0.14%)479.3 V1.14 V (0.24%)53.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.55 V (0.11%)479.4 V0.91 V (0.19%)43.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.46 V (0.1%)479.5 V0.76 V (0.16%)35.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.37 V (0.08%)479.6 V0.61 V (0.13%)28.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.28 V (0.06%)479.7 V0.46 V (0.09%)21.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 275 feet one-way at 480V (3-Phase), you need 6 AWG copper wire. This produces a voltage drop of 10.51V (2.19%) and delivers 469.5V at the load.

What size aluminum wire is required for 45 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 10.9V (2.27%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.