🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.42V (2.68%)
Voltage at Load End238.1 VLoss: 1.95 V (1070.8 W)
Power & Breaker (125%)132.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A948.62 V (395.26%)0.0 V1564.77 V (651.99%)521739.2 WDrop/Amp High
12 AWG3.31 mm²20 A596.11 V (248.38%)0.0 V983.3 V (409.71%)327860.3 WDrop/Amp High
10 AWG5.26 mm²30 A375.12 V (156.3%)0.0 V618.77 V (257.82%)206315.1 WDrop/Amp High
8 AWG8.37 mm²50 A235.74 V (98.22%)4.3 V388.86 V (162.02%)129655.6 WDrop/Amp High
6 AWG13.3 mm²65 A148.36 V (61.81%)91.6 V244.72 V (101.97%)81595.3 WDrop/Amp High
4 AWG21.15 mm²85 A93.29 V (38.87%)146.7 V153.89 V (64.12%)51310.5 WDrop/Amp High
3 AWG26.67 mm²100 A73.98 V (30.83%)166.0 V122.04 V (50.85%)40690.6 WDrop/Amp High
2 AWG33.62 mm²115 A58.69 V (24.45%)181.3 V96.81 V (40.34%)32278.9 WDrop/Amp High
1 AWG42.41 mm²130 A46.52 V (19.39%)193.5 V76.74 V (31.98%)25588.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A36.89 V (15.37%)203.1 V60.85 V (25.35%)20288.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A29.26 V (12.19%)210.7 V48.27 V (20.11%)16094.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.21 V (9.67%)216.8 V38.29 V (15.95%)12765.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.41 V (7.67%)221.6 V30.36 V (12.65%)10123.3 WDrop/Amp High
250 kcmil126.7 mm²255 A15.57 V (6.49%)224.4 V25.69 V (10.7%)8565.3 WDrop/Amp High
300 kcmil152.0 mm²285 A12.98 V (5.41%)227.0 V21.41 V (8.92%)7139.6 WDrop/Amp High
350 kcmil177.3 mm²310 A11.13 V (4.64%)228.9 V18.36 V (7.65%)6120.8 WDrop/Amp High
400 kcmil202.7 mm²335 A9.73 V (4.06%)230.3 V16.06 V (6.69%)5353.8 WDrop/Amp High
500 kcmil253.4 mm²380 A7.79 V (3.24%)232.2 V12.84 V (5.35%)4282.6 WDrop/Amp High
600 kcmil304.0 mm²420 A6.49 V (2.7%)233.5 V10.71 V (4.46%)3569.8 WDrop/Amp High
750 kcmil380.0 mm²475 A5.19 V (2.16%)234.8 V8.57 V (3.57%)2855.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.89 V (1.62%)236.1 V6.42 V (2.68%)2141.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 275 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.95V (0.81%) and delivers 238.1V at the load.

What size aluminum wire is required for 550 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.42V (2.68%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.