🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.46%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 12.28V (2.56%)
Voltage at Load End468.2 VLoss: 11.83 V (1434.0 W)
Power & Breaker (125%)58.2 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A304.17 V (63.37%)175.8 V501.74 V (104.53%)36878.5 WDrop/Amp High
12 AWG3.31 mm²20 A191.14 V (39.82%)288.9 V315.29 V (65.69%)23174.4 WDrop/Amp High
10 AWG5.26 mm²30 A120.28 V (25.06%)359.7 V198.4 V (41.33%)14583.1 WDrop/Amp High
8 AWG8.37 mm²50 A75.59 V (15.75%)404.4 V124.68 V (25.98%)9164.5 WDrop/Amp High
6 AWG13.3 mm²65 A47.57 V (9.91%)432.4 V78.47 V (16.35%)5767.5 WDrop/Amp High
4 AWG21.15 mm²85 A29.91 V (6.23%)450.1 V49.34 V (10.28%)3626.8 WDrop/Amp High
3 AWG26.67 mm²100 A23.72 V (4.94%)456.3 V39.13 V (8.15%)2876.2 W~ ≤5%
2 AWG33.62 mm²115 A18.82 V (3.92%)461.2 V31.04 V (6.47%)2281.6 W~ ≤5%
1 AWG42.41 mm²130 A14.92 V (3.11%)465.1 V24.61 V (5.13%)1808.7 W~ ≤5%
1/0 AWG53.49 mm²150 A11.83 V (2.46%)468.2 V19.51 V (4.06%)1434.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A9.38 V (1.95%)470.6 V15.48 V (3.22%)1137.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A7.44 V (1.55%)472.6 V12.28 V (2.56%)902.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.9 V (1.23%)474.1 V9.74 V (2.03%)715.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.99 V (1.04%)475.0 V8.24 V (1.72%)605.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.16 V (0.87%)475.8 V6.87 V (1.43%)504.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.57 V (0.74%)476.4 V5.89 V (1.23%)432.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.12 V (0.65%)476.9 V5.15 V (1.07%)378.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.5 V (0.52%)477.5 V4.12 V (0.86%)302.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.08 V (0.43%)477.9 V3.43 V (0.72%)252.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.66 V (0.35%)478.3 V2.75 V (0.57%)201.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.25 V (0.26%)478.8 V2.06 V (0.43%)151.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 800 feet one-way at 480V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 11.83V (2.46%) and delivers 468.2V at the load.

What size aluminum wire is required for 70 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 12.28V (2.56%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.