🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 400 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 5.39V (2.59%)
Voltage at Load End202.2 VLoss: 5.85 V (1114.1 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 400 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A238.99 V (114.9%)0.0 V394.22 V (189.53%)45533.6 WDrop/Amp High
12 AWG3.31 mm²20 A150.18 V (72.2%)57.8 V247.73 V (119.1%)28613.3 WDrop/Amp High
10 AWG5.26 mm²30 A94.51 V (45.44%)113.5 V155.89 V (74.95%)18005.7 WDrop/Amp High
8 AWG8.37 mm²50 A59.39 V (28.55%)148.6 V97.97 V (47.1%)11315.4 WDrop/Amp High
6 AWG13.3 mm²65 A37.38 V (17.97%)170.6 V61.65 V (29.64%)7121.0 WDrop/Amp High
4 AWG21.15 mm²85 A23.5 V (11.3%)184.5 V38.77 V (18.64%)4478.0 WDrop/Amp High
3 AWG26.67 mm²100 A18.64 V (8.96%)189.4 V30.75 V (14.78%)3551.2 WDrop/Amp High
2 AWG33.62 mm²115 A14.79 V (7.11%)193.2 V24.39 V (11.73%)2817.1 WDrop/Amp High
1 AWG42.41 mm²130 A11.72 V (5.64%)196.3 V19.33 V (9.3%)2233.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.29 V (4.47%)198.7 V15.33 V (7.37%)1770.6 W~ ≤5%
2/0 AWG67.43 mm²175 A7.37 V (3.54%)200.6 V12.16 V (5.85%)1404.6 W~ ≤5%
3/0 AWG85.01 mm²200 A5.85 V (2.81%)202.2 V9.65 V (4.64%)1114.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.64 V (2.23%)203.4 V7.65 V (3.68%)883.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.92 V (1.89%)204.1 V6.47 V (3.11%)747.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.27 V (1.57%)204.7 V5.39 V (2.59%)623.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.8 V (1.35%)205.2 V4.62 V (2.22%)534.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.45 V (1.18%)205.5 V4.05 V (1.94%)467.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.96 V (0.94%)206.0 V3.24 V (1.56%)373.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.64 V (0.79%)206.4 V2.7 V (1.3%)311.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.31 V (0.63%)206.7 V2.16 V (1.04%)249.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.98 V (0.47%)207.0 V1.62 V (0.78%)186.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 400 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 400 feet one-way at 208V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 5.85V (2.81%) and delivers 202.2V at the load.

What size aluminum wire is required for 110 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 5.39V (2.59%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.