🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 800 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.7%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 5.39V (2.59%)
Voltage at Load End202.4 VLoss: 5.61 V (1068.4 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 800 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A477.98 V (229.8%)0.0 V788.44 V (379.06%)91067.2 WDrop/Amp High
12 AWG3.31 mm²20 A300.36 V (144.4%)0.0 V495.46 V (238.2%)57226.5 WDrop/Amp High
10 AWG5.26 mm²30 A189.01 V (90.87%)19.0 V311.78 V (149.89%)36011.4 WDrop/Amp High
8 AWG8.37 mm²50 A118.78 V (57.11%)89.2 V195.93 V (94.2%)22630.8 WDrop/Amp High
6 AWG13.3 mm²65 A74.75 V (35.94%)133.2 V123.31 V (59.28%)14242.1 WDrop/Amp High
4 AWG21.15 mm²85 A47.01 V (22.6%)161.0 V77.54 V (37.28%)8956.0 WDrop/Amp High
3 AWG26.67 mm²100 A37.28 V (17.92%)170.7 V61.49 V (29.56%)7102.4 WDrop/Amp High
2 AWG33.62 mm²115 A29.57 V (14.22%)178.4 V48.78 V (23.45%)5634.1 WDrop/Amp High
1 AWG42.41 mm²130 A23.44 V (11.27%)184.6 V38.67 V (18.59%)4466.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A18.59 V (8.94%)189.4 V30.66 V (14.74%)3541.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.74 V (7.09%)193.3 V24.32 V (11.69%)2809.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.7 V (5.62%)196.3 V19.29 V (9.27%)2228.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.27 V (4.46%)198.7 V15.3 V (7.35%)1767.0 W~ ≤5%
250 kcmil126.7 mm²255 A7.85 V (3.77%)200.2 V12.94 V (6.22%)1495.0 W~ ≤5%
300 kcmil152.0 mm²285 A6.54 V (3.14%)201.5 V10.79 V (5.19%)1246.2 W~ ≤5%
350 kcmil177.3 mm²310 A5.61 V (2.7%)202.4 V9.25 V (4.45%)1068.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.9 V (2.36%)203.1 V8.09 V (3.89%)934.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.92 V (1.89%)204.1 V6.47 V (3.11%)747.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.27 V (1.57%)204.7 V5.39 V (2.59%)623.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.62 V (1.26%)205.4 V4.32 V (2.07%)498.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.96 V (0.94%)206.0 V3.24 V (1.56%)373.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 800 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 800 feet one-way at 208V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 5.61V (2.7%) and delivers 202.4V at the load.

What size aluminum wire is required for 110 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 5.39V (2.59%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.