⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.66%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 7.08V (2.95%)
Voltage at Load End233.6 VLoss: 6.4 V (1938.6 W)
Power & Breaker (125%)72.75 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A261.39 V (108.91%)0.0 V431.18 V (179.66%)79231.1 WDrop/Amp High
12 AWG3.31 mm²20 A164.26 V (68.44%)75.7 V270.95 V (112.9%)49788.7 WDrop/Amp High
10 AWG5.26 mm²30 A103.37 V (43.07%)136.6 V170.5 V (71.04%)31330.9 WDrop/Amp High
8 AWG8.37 mm²50 A64.96 V (27.07%)175.0 V107.15 V (44.65%)19689.4 WDrop/Amp High
6 AWG13.3 mm²65 A40.88 V (17.03%)199.1 V67.43 V (28.1%)12391.0 WDrop/Amp High
4 AWG21.15 mm²85 A25.71 V (10.71%)214.3 V42.4 V (17.67%)7792.0 WDrop/Amp High
3 AWG26.67 mm²100 A20.39 V (8.49%)219.6 V33.63 V (14.01%)6179.3 WDrop/Amp High
2 AWG33.62 mm²115 A16.17 V (6.74%)223.8 V26.68 V (11.12%)4901.9 WDrop/Amp High
1 AWG42.41 mm²130 A12.82 V (5.34%)227.2 V21.15 V (8.81%)3885.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.16 V (4.24%)229.8 V16.77 V (6.99%)3081.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.06 V (3.36%)231.9 V13.3 V (5.54%)2444.0 W~ ≤5%
3/0 AWG85.01 mm²200 A6.4 V (2.66%)233.6 V10.55 V (4.4%)1938.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.07 V (2.11%)234.9 V8.37 V (3.49%)1537.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.29 V (1.79%)235.7 V7.08 V (2.95%)1300.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.58 V (1.49%)236.4 V5.9 V (2.46%)1084.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.07 V (1.28%)236.9 V5.06 V (2.11%)929.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.68 V (1.12%)237.3 V4.42 V (1.84%)813.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.15 V (0.89%)237.9 V3.54 V (1.47%)650.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.79 V (0.75%)238.2 V2.95 V (1.23%)542.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.43 V (0.6%)238.6 V2.36 V (0.98%)433.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.07 V (0.45%)238.9 V1.77 V (0.74%)325.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 275 feet one-way at 240V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 6.4V (2.66%) and delivers 233.6V at the load.

What size aluminum wire is required for 175 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 7.08V (2.95%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.