⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.09%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.28V (6.9%)
Voltage at Load End117.5 VLoss: 2.51 V (815.8 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1223.01 V (1019.17%)0.0 V2017.39 V (1681.16%)397478.2 WDrop/Amp High
12 AWG3.31 mm²20 A768.54 V (640.45%)0.0 V1267.73 V (1056.44%)249774.9 WDrop/Amp High
10 AWG5.26 mm²30 A483.62 V (403.02%)0.0 V797.75 V (664.79%)157177.7 WDrop/Amp High
8 AWG8.37 mm²50 A303.93 V (253.27%)0.0 V501.34 V (417.78%)98776.0 WDrop/Amp High
6 AWG13.3 mm²65 A191.27 V (159.39%)0.0 V315.5 V (262.92%)62162.0 WDrop/Amp High
4 AWG21.15 mm²85 A120.28 V (100.23%)0.0 V198.4 V (165.33%)39090.1 WDrop/Amp High
3 AWG26.67 mm²100 A95.38 V (79.49%)24.6 V157.34 V (131.11%)30999.4 WDrop/Amp High
2 AWG33.62 mm²115 A75.67 V (63.05%)44.3 V124.81 V (104.01%)24591.2 WDrop/Amp High
1 AWG42.41 mm²130 A59.98 V (49.99%)60.0 V98.94 V (82.45%)19494.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A47.56 V (39.63%)72.4 V78.45 V (65.37%)15456.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A37.73 V (31.44%)82.3 V62.23 V (51.86%)12260.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.92 V (24.94%)90.1 V49.36 V (41.13%)9725.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.73 V (19.78%)96.3 V39.14 V (32.62%)7712.3 WDrop/Amp High
250 kcmil126.7 mm²255 A20.08 V (16.73%)99.9 V33.12 V (27.6%)6525.3 WDrop/Amp High
300 kcmil152.0 mm²285 A16.74 V (13.95%)103.3 V27.61 V (23.01%)5439.2 WDrop/Amp High
350 kcmil177.3 mm²310 A14.35 V (11.96%)105.7 V23.67 V (19.72%)4663.0 WDrop/Amp High
400 kcmil202.7 mm²335 A12.55 V (10.46%)107.5 V20.7 V (17.25%)4078.7 WDrop/Amp High
500 kcmil253.4 mm²380 A10.04 V (8.37%)110.0 V16.56 V (13.8%)3262.6 WDrop/Amp High
600 kcmil304.0 mm²420 A8.37 V (6.97%)111.6 V13.8 V (11.5%)2719.6 WDrop/Amp High
750 kcmil380.0 mm²475 A6.69 V (5.58%)113.3 V11.04 V (9.2%)2175.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.02 V (4.18%)115.0 V8.28 V (6.9%)1631.6 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 600 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.51V (2.09%) and delivers 117.5V at the load.

What size aluminum wire is required for 325 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.28V (6.9%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.