🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 800 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.04V (4.6%)
Voltage at Load End233.3 VLoss: 6.69 V (2175.5 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1630.68 V (679.45%)0.0 V2689.86 V (1120.78%)529971.0 WDrop/Amp High
12 AWG3.31 mm²20 A1024.72 V (426.97%)0.0 V1690.3 V (704.29%)333033.1 WDrop/Amp High
10 AWG5.26 mm²30 A644.83 V (268.68%)0.0 V1063.67 V (443.2%)209570.3 WDrop/Amp High
8 AWG8.37 mm²50 A405.23 V (168.85%)0.0 V668.45 V (278.52%)131701.3 WDrop/Amp High
6 AWG13.3 mm²65 A255.02 V (106.26%)0.0 V420.67 V (175.28%)82882.7 WDrop/Amp High
4 AWG21.15 mm²85 A160.37 V (66.82%)79.6 V264.53 V (110.22%)52120.1 WDrop/Amp High
3 AWG26.67 mm²100 A127.18 V (52.99%)112.8 V209.78 V (87.41%)41332.6 WDrop/Amp High
2 AWG33.62 mm²115 A100.89 V (42.04%)139.1 V166.42 V (69.34%)32788.2 WDrop/Amp High
1 AWG42.41 mm²130 A79.98 V (33.32%)160.0 V131.92 V (54.97%)25992.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A63.41 V (26.42%)176.6 V104.6 V (43.58%)20608.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A50.3 V (20.96%)189.7 V82.97 V (34.57%)16347.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A39.9 V (16.62%)200.1 V65.81 V (27.42%)12967.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A31.64 V (13.18%)208.4 V52.19 V (21.75%)10283.0 WDrop/Amp High
250 kcmil126.7 mm²255 A26.77 V (11.15%)213.2 V44.16 V (18.4%)8700.4 WDrop/Amp High
300 kcmil152.0 mm²285 A22.31 V (9.3%)217.7 V36.81 V (15.34%)7252.2 WDrop/Amp High
350 kcmil177.3 mm²310 A19.13 V (7.97%)220.9 V31.56 V (13.15%)6217.4 WDrop/Amp High
400 kcmil202.7 mm²335 A16.73 V (6.97%)223.3 V27.6 V (11.5%)5438.3 WDrop/Amp High
500 kcmil253.4 mm²380 A13.39 V (5.58%)226.6 V22.08 V (9.2%)4350.2 WDrop/Amp High
600 kcmil304.0 mm²420 A11.16 V (4.65%)228.8 V18.4 V (7.67%)3626.1 W~ ≤5%
750 kcmil380.0 mm²475 A8.93 V (3.72%)231.1 V14.72 V (6.13%)2900.9 W~ ≤5%
1000 kcmil506.7 mm²545 A6.69 V (2.79%)233.3 V11.04 V (4.6%)2175.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 800 feet one-way at 240V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 6.69V (2.79%) and delivers 233.3V at the load.

What size aluminum wire is required for 325 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.04V (4.6%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.