⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.42%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.56V (3.98%)
Voltage at Load End234.2 VLoss: 5.8 V (3263.3 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1412.21 V (588.42%)0.0 V2329.49 V (970.62%)794956.5 WDrop/Amp High
12 AWG3.31 mm²20 A887.43 V (369.76%)0.0 V1463.85 V (609.94%)499549.7 WDrop/Amp High
10 AWG5.26 mm²30 A558.44 V (232.68%)0.0 V921.17 V (383.82%)314355.4 WDrop/Amp High
8 AWG8.37 mm²50 A350.94 V (146.23%)0.0 V578.89 V (241.21%)197551.9 WDrop/Amp High
6 AWG13.3 mm²65 A220.86 V (92.02%)19.1 V364.31 V (151.8%)124324.0 WDrop/Amp High
4 AWG21.15 mm²85 A138.88 V (57.87%)101.1 V229.09 V (95.46%)78180.1 WDrop/Amp High
3 AWG26.67 mm²100 A110.14 V (45.89%)129.9 V181.68 V (75.7%)61998.9 WDrop/Amp High
2 AWG33.62 mm²115 A87.37 V (36.4%)152.6 V144.12 V (60.05%)49182.3 WDrop/Amp High
1 AWG42.41 mm²130 A69.26 V (28.86%)170.7 V114.25 V (47.6%)38988.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A54.91 V (22.88%)185.1 V90.58 V (37.74%)30912.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A43.56 V (18.15%)196.4 V71.86 V (29.94%)24521.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A34.55 V (14.4%)205.4 V57.0 V (23.75%)19450.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A27.4 V (11.42%)212.6 V45.2 V (18.83%)15424.5 WDrop/Amp High
250 kcmil126.7 mm²255 A23.18 V (9.66%)216.8 V38.24 V (15.93%)13050.6 WDrop/Amp High
300 kcmil152.0 mm²285 A19.32 V (8.05%)220.7 V31.88 V (13.28%)10878.4 WDrop/Amp High
350 kcmil177.3 mm²310 A16.57 V (6.9%)223.4 V27.33 V (11.39%)9326.1 WDrop/Amp High
400 kcmil202.7 mm²335 A14.49 V (6.04%)225.5 V23.9 V (9.96%)8157.4 WDrop/Amp High
500 kcmil253.4 mm²380 A11.59 V (4.83%)228.4 V19.12 V (7.97%)6525.3 W~ ≤5%
600 kcmil304.0 mm²420 A9.66 V (4.03%)230.3 V15.94 V (6.64%)5439.2 W~ ≤5%
750 kcmil380.0 mm²475 A7.73 V (3.22%)232.3 V12.75 V (5.31%)4351.3 W~ ≤5%
1000 kcmil506.7 mm²545 A5.8 V (2.42%)234.2 V9.56 V (3.98%)3263.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 800 feet one-way at 240V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 5.8V (2.42%) and delivers 234.2V at the load.

What size aluminum wire is required for 325 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.56V (3.98%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.