🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 15.63V (7.51%)
Voltage at Load End203.3 VLoss: 4.74 V (3487.8 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2308.42 V (1109.82%)0.0 V3807.82 V (1830.68%)1699278.3 WDrop/Amp High
12 AWG3.31 mm²20 A1450.61 V (697.41%)0.0 V2392.83 V (1150.4%)1067824.4 WDrop/Amp High
10 AWG5.26 mm²30 A912.84 V (438.86%)0.0 V1505.75 V (723.92%)671958.0 WDrop/Amp High
8 AWG8.37 mm²50 A573.66 V (275.8%)0.0 V946.27 V (454.94%)422281.8 WDrop/Amp High
6 AWG13.3 mm²65 A361.02 V (173.57%)0.0 V595.51 V (286.3%)265751.8 WDrop/Amp High
4 AWG21.15 mm²85 A227.02 V (109.15%)0.0 V374.48 V (180.04%)167115.8 WDrop/Amp High
3 AWG26.67 mm²100 A180.03 V (86.55%)28.0 V296.97 V (142.78%)132527.1 WDrop/Amp High
2 AWG33.62 mm²115 A142.82 V (68.66%)65.2 V235.58 V (113.26%)105130.8 WDrop/Amp High
1 AWG42.41 mm²130 A113.22 V (54.43%)94.8 V186.75 V (89.79%)83341.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A89.76 V (43.16%)118.2 V148.07 V (71.19%)66077.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A71.21 V (34.23%)136.8 V117.46 V (56.47%)52417.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A56.48 V (27.15%)151.5 V93.17 V (44.79%)41577.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A44.79 V (21.53%)163.2 V73.88 V (35.52%)32971.1 WDrop/Amp High
250 kcmil126.7 mm²255 A37.9 V (18.22%)170.1 V62.51 V (30.05%)27896.6 WDrop/Amp High
300 kcmil152.0 mm²285 A31.59 V (15.19%)176.4 V52.11 V (25.05%)23253.3 WDrop/Amp High
350 kcmil177.3 mm²310 A27.08 V (13.02%)180.9 V44.67 V (21.48%)19935.1 WDrop/Amp High
400 kcmil202.7 mm²335 A23.69 V (11.39%)184.3 V39.07 V (18.79%)17437.1 WDrop/Amp High
500 kcmil253.4 mm²380 A18.95 V (9.11%)189.1 V31.26 V (15.03%)13948.3 WDrop/Amp High
600 kcmil304.0 mm²420 A15.79 V (7.59%)192.2 V26.05 V (12.53%)11626.6 WDrop/Amp High
750 kcmil380.0 mm²475 A12.64 V (6.07%)195.4 V20.84 V (10.02%)9301.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.48 V (4.56%)198.5 V15.63 V (7.51%)6975.5 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 1000 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.74V (2.28%) and delivers 203.3V at the load.

What size aluminum wire is required for 425 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 15.63V (7.51%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.