⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 200 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.43%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.61V (3.01%)
Voltage at Load End117.1 VLoss: 2.92 V (1240.2 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 200 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A533.11 V (444.26%)0.0 V879.38 V (732.81%)226570.4 WDrop/Amp High
12 AWG3.31 mm²20 A335.0 V (279.17%)0.0 V552.6 V (460.5%)142376.6 WDrop/Amp High
10 AWG5.26 mm²30 A210.81 V (175.68%)0.0 V347.74 V (289.78%)89594.4 WDrop/Amp High
8 AWG8.37 mm²50 A132.48 V (110.4%)0.0 V218.53 V (182.11%)56304.2 WDrop/Amp High
6 AWG13.3 mm²65 A83.37 V (69.48%)36.6 V137.53 V (114.61%)35433.6 WDrop/Amp High
4 AWG21.15 mm²85 A52.43 V (43.69%)67.6 V86.48 V (72.07%)22282.1 WDrop/Amp High
3 AWG26.67 mm²100 A41.58 V (34.65%)78.4 V68.58 V (57.15%)17670.3 WDrop/Amp High
2 AWG33.62 mm²115 A32.98 V (27.49%)87.0 V54.41 V (45.34%)14017.4 WDrop/Amp High
1 AWG42.41 mm²130 A26.15 V (21.79%)93.9 V43.13 V (35.94%)11112.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.73 V (17.28%)99.3 V34.2 V (28.5%)8810.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.44 V (13.7%)103.6 V27.13 V (22.6%)6989.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.04 V (10.87%)107.0 V21.52 V (17.93%)5543.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.34 V (8.62%)109.7 V17.06 V (14.22%)4396.1 WDrop/Amp High
250 kcmil126.7 mm²255 A8.75 V (7.29%)111.2 V14.44 V (12.03%)3719.5 WDrop/Amp High
300 kcmil152.0 mm²285 A7.3 V (6.08%)112.7 V12.03 V (10.03%)3100.4 WDrop/Amp High
350 kcmil177.3 mm²310 A6.25 V (5.21%)113.7 V10.32 V (8.6%)2658.0 WDrop/Amp High
400 kcmil202.7 mm²335 A5.47 V (4.56%)114.5 V9.02 V (7.52%)2324.9 WDrop/Amp High
500 kcmil253.4 mm²380 A4.38 V (3.65%)115.6 V7.22 V (6.02%)1859.8 WDrop/Amp High
600 kcmil304.0 mm²420 A3.65 V (3.04%)116.4 V6.02 V (5.01%)1550.2 WDrop/Amp High
750 kcmil380.0 mm²475 A2.92 V (2.43%)117.1 V4.81 V (4.01%)1240.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.19 V (1.82%)117.8 V3.61 V (3.01%)930.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 200 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 200 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.92V (2.43%) and delivers 117.1V at the load.

What size aluminum wire is required for 425 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.61V (3.01%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.