🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 250 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.51V (3.76%)
Voltage at Load End117.3 VLoss: 2.74 V (1162.6 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 250 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A666.38 V (555.32%)0.0 V1099.22 V (916.02%)283213.1 WDrop/Amp High
12 AWG3.31 mm²20 A418.75 V (348.96%)0.0 V690.75 V (575.62%)177970.7 WDrop/Amp High
10 AWG5.26 mm²30 A263.51 V (219.59%)0.0 V434.67 V (362.23%)111993.0 WDrop/Amp High
8 AWG8.37 mm²50 A165.6 V (138.0%)0.0 V273.16 V (227.64%)70380.3 WDrop/Amp High
6 AWG13.3 mm²65 A104.22 V (86.85%)15.8 V171.91 V (143.26%)44292.0 WDrop/Amp High
4 AWG21.15 mm²85 A65.54 V (54.61%)54.5 V108.1 V (90.09%)27852.6 WDrop/Amp High
3 AWG26.67 mm²100 A51.97 V (43.31%)68.0 V85.73 V (71.44%)22087.9 WDrop/Amp High
2 AWG33.62 mm²115 A41.23 V (34.36%)78.8 V68.01 V (56.67%)17521.8 WDrop/Amp High
1 AWG42.41 mm²130 A32.68 V (27.24%)87.3 V53.91 V (44.93%)13890.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.91 V (21.59%)94.1 V42.74 V (35.62%)11013.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.56 V (17.13%)99.4 V33.91 V (28.26%)8736.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.3 V (13.59%)103.7 V26.9 V (22.41%)6929.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.93 V (10.77%)107.1 V21.33 V (17.77%)5495.2 WDrop/Amp High
250 kcmil126.7 mm²255 A10.94 V (9.12%)109.1 V18.05 V (15.04%)4649.4 WDrop/Amp High
300 kcmil152.0 mm²285 A9.12 V (7.6%)110.9 V15.04 V (12.53%)3875.5 WDrop/Amp High
350 kcmil177.3 mm²310 A7.82 V (6.51%)112.2 V12.9 V (10.75%)3322.5 WDrop/Amp High
400 kcmil202.7 mm²335 A6.84 V (5.7%)113.2 V11.28 V (9.4%)2906.2 WDrop/Amp High
500 kcmil253.4 mm²380 A5.47 V (4.56%)114.5 V9.02 V (7.52%)2324.7 WDrop/Amp High
600 kcmil304.0 mm²420 A4.56 V (3.8%)115.4 V7.52 V (6.27%)1937.8 WDrop/Amp High
750 kcmil380.0 mm²475 A3.65 V (3.04%)116.4 V6.02 V (5.01%)1550.2 W~ ≤5%
1000 kcmil506.7 mm²545 A2.74 V (2.28%)117.3 V4.51 V (3.76%)1162.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 250 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 250 feet one-way at 120V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 2.74V (2.28%) and delivers 117.3V at the load.

What size aluminum wire is required for 425 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.51V (3.76%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.