🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 275 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.51%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.96V (4.14%)
Voltage at Load End117.0 VLoss: 3.01 V (1278.8 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 275 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A733.02 V (610.85%)0.0 V1209.14 V (1007.62%)311534.4 WDrop/Amp High
12 AWG3.31 mm²20 A460.63 V (383.86%)0.0 V759.82 V (633.19%)195767.8 WDrop/Amp High
10 AWG5.26 mm²30 A289.86 V (241.55%)0.0 V478.14 V (398.45%)123192.3 WDrop/Amp High
8 AWG8.37 mm²50 A182.16 V (151.8%)0.0 V300.48 V (250.4%)77418.3 WDrop/Amp High
6 AWG13.3 mm²65 A114.64 V (95.53%)5.4 V189.1 V (157.58%)48721.2 WDrop/Amp High
4 AWG21.15 mm²85 A72.09 V (60.07%)47.9 V118.91 V (99.09%)30637.9 WDrop/Amp High
3 AWG26.67 mm²100 A57.17 V (47.64%)62.8 V94.3 V (78.58%)24296.6 WDrop/Amp High
2 AWG33.62 mm²115 A45.35 V (37.79%)74.6 V74.81 V (62.34%)19274.0 WDrop/Amp High
1 AWG42.41 mm²130 A35.95 V (29.96%)84.0 V59.3 V (49.42%)15279.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A28.5 V (23.75%)91.5 V47.02 V (39.18%)12114.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A22.61 V (18.84%)97.4 V37.3 V (31.08%)9609.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.94 V (14.95%)102.1 V29.58 V (24.65%)7622.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.22 V (11.85%)105.8 V23.46 V (19.55%)6044.7 WDrop/Amp High
250 kcmil126.7 mm²255 A12.03 V (10.03%)108.0 V19.85 V (16.54%)5114.4 WDrop/Amp High
300 kcmil152.0 mm²285 A10.03 V (8.36%)110.0 V16.55 V (13.79%)4263.1 WDrop/Amp High
350 kcmil177.3 mm²310 A8.6 V (7.17%)111.4 V14.19 V (11.82%)3654.8 WDrop/Amp High
400 kcmil202.7 mm²335 A7.52 V (6.27%)112.5 V12.41 V (10.34%)3196.8 WDrop/Amp High
500 kcmil253.4 mm²380 A6.02 V (5.01%)114.0 V9.93 V (8.27%)2557.2 WDrop/Amp High
600 kcmil304.0 mm²420 A5.02 V (4.18%)115.0 V8.27 V (6.89%)2131.6 WDrop/Amp High
750 kcmil380.0 mm²475 A4.01 V (3.34%)116.0 V6.62 V (5.52%)1705.2 W~ ≤5%
1000 kcmil506.7 mm²545 A3.01 V (2.51%)117.0 V4.96 V (4.14%)1278.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 275 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 275 feet one-way at 120V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 3.01V (2.51%) and delivers 117.0V at the load.

What size aluminum wire is required for 425 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.96V (4.14%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.