⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 275 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)9× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.96V (41.36%)
Voltage at Load End11.7 VLoss: 0.33 V (142.1 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 275 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A733.02 V (6108.52%)0.0 V1209.14 V (10076.2%)311534.4 WDrop/Amp High
12 AWG3.31 mm²20 A460.63 V (3838.58%)0.0 V759.82 V (6331.87%)195767.8 WDrop/Amp High
10 AWG5.26 mm²30 A289.86 V (2415.54%)0.0 V478.14 V (3984.5%)123192.3 WDrop/Amp High
8 AWG8.37 mm²50 A182.16 V (1518.01%)0.0 V300.48 V (2504.0%)77418.3 WDrop/Amp High
6 AWG13.3 mm²65 A114.64 V (955.32%)0.0 V189.1 V (1575.83%)48721.2 WDrop/Amp High
4 AWG21.15 mm²85 A72.09 V (600.74%)0.0 V118.91 V (990.95%)30637.9 WDrop/Amp High
3 AWG26.67 mm²100 A57.17 V (476.4%)0.0 V94.3 V (785.85%)24296.6 WDrop/Amp High
2 AWG33.62 mm²115 A45.35 V (377.92%)0.0 V74.81 V (623.39%)19274.0 WDrop/Amp High
1 AWG42.41 mm²130 A35.95 V (299.59%)0.0 V59.3 V (494.19%)15279.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A28.5 V (237.53%)0.0 V47.02 V (391.82%)12114.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A22.61 V (188.43%)0.0 V37.3 V (310.82%)9609.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.94 V (149.46%)0.0 V29.58 V (246.54%)7622.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.22 V (118.52%)0.0 V23.46 V (195.51%)6044.7 WDrop/Amp High
250 kcmil126.7 mm²255 A12.03 V (100.28%)0.0 V19.85 V (165.42%)5114.4 WDrop/Amp High
300 kcmil152.0 mm²285 A10.03 V (83.59%)2.0 V16.55 V (137.88%)4263.1 WDrop/Amp High
350 kcmil177.3 mm²310 A8.6 V (71.66%)3.4 V14.19 V (118.21%)3654.8 WDrop/Amp High
400 kcmil202.7 mm²335 A7.52 V (62.68%)4.5 V12.41 V (103.4%)3196.8 WDrop/Amp High
500 kcmil253.4 mm²380 A6.02 V (50.14%)6.0 V9.93 V (82.71%)2557.2 WDrop/Amp High
600 kcmil304.0 mm²420 A5.02 V (41.8%)7.0 V8.27 V (68.94%)2131.6 WDrop/Amp High
750 kcmil380.0 mm²475 A4.01 V (33.44%)8.0 V6.62 V (55.15%)1705.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.01 V (25.08%)9.0 V4.96 V (41.36%)1278.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 275 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 275 feet one-way at 12V (DC), you need 9× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.79%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.96V (41.36%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.