🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 400 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.43%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.25V (3.01%)
Voltage at Load End202.9 VLoss: 5.05 V (3720.5 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 400 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A923.37 V (443.93%)0.0 V1523.13 V (732.27%)679711.3 WDrop/Amp High
12 AWG3.31 mm²20 A580.24 V (278.96%)0.0 V957.13 V (460.16%)427129.8 WDrop/Amp High
10 AWG5.26 mm²30 A365.13 V (175.55%)0.0 V602.3 V (289.57%)268783.2 WDrop/Amp High
8 AWG8.37 mm²50 A229.46 V (110.32%)0.0 V378.51 V (181.97%)168912.7 WDrop/Amp High
6 AWG13.3 mm²65 A144.41 V (69.43%)63.6 V238.2 V (114.52%)106300.7 WDrop/Amp High
4 AWG21.15 mm²85 A90.81 V (43.66%)117.2 V149.79 V (72.02%)66846.3 WDrop/Amp High
3 AWG26.67 mm²100 A72.01 V (34.62%)136.0 V118.79 V (57.11%)53010.9 WDrop/Amp High
2 AWG33.62 mm²115 A57.13 V (27.46%)150.9 V94.23 V (45.3%)42052.3 WDrop/Amp High
1 AWG42.41 mm²130 A45.29 V (21.77%)162.7 V74.7 V (35.91%)33336.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A35.91 V (17.26%)172.1 V59.23 V (28.47%)26431.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A28.48 V (13.69%)179.5 V46.98 V (22.59%)20966.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A22.59 V (10.86%)185.4 V37.27 V (17.92%)16631.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.92 V (8.61%)190.1 V29.55 V (14.21%)13188.4 WDrop/Amp High
250 kcmil126.7 mm²255 A15.16 V (7.29%)192.8 V25.0 V (12.02%)11158.6 WDrop/Amp High
300 kcmil152.0 mm²285 A12.64 V (6.07%)195.4 V20.84 V (10.02%)9301.3 WDrop/Amp High
350 kcmil177.3 mm²310 A10.83 V (5.21%)197.2 V17.87 V (8.59%)7974.1 WDrop/Amp High
400 kcmil202.7 mm²335 A9.48 V (4.56%)198.5 V15.63 V (7.51%)6974.8 WDrop/Amp High
500 kcmil253.4 mm²380 A7.58 V (3.64%)200.4 V12.5 V (6.01%)5579.3 WDrop/Amp High
600 kcmil304.0 mm²420 A6.32 V (3.04%)201.7 V10.42 V (5.01%)4650.7 WDrop/Amp High
750 kcmil380.0 mm²475 A5.05 V (2.43%)202.9 V8.34 V (4.01%)3720.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.79 V (1.82%)204.2 V6.25 V (3.01%)2790.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 400 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 400 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 5.05V (2.43%) and delivers 202.9V at the load.

What size aluminum wire is required for 425 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.25V (3.01%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.