🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 450 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)14× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.93%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.12V (67.68%)
Voltage at Load End11.7 VLoss: 0.35 V (149.5 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 450 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1199.49 V (9995.75%)0.0 V1978.6 V (16488.32%)509783.5 WDrop/Amp High
12 AWG3.31 mm²20 A753.76 V (6281.32%)0.0 V1243.35 V (10361.24%)320347.3 WDrop/Amp High
10 AWG5.26 mm²30 A474.32 V (3952.69%)0.0 V782.41 V (6520.1%)201587.4 WDrop/Amp High
8 AWG8.37 mm²50 A298.08 V (2484.01%)0.0 V491.69 V (4097.46%)126684.5 WDrop/Amp High
6 AWG13.3 mm²65 A187.59 V (1563.25%)0.0 V309.44 V (2578.63%)79725.5 WDrop/Amp High
4 AWG21.15 mm²85 A117.96 V (983.03%)0.0 V194.59 V (1621.55%)50134.7 WDrop/Amp High
3 AWG26.67 mm²100 A93.55 V (779.57%)0.0 V154.31 V (1285.93%)39758.1 WDrop/Amp High
2 AWG33.62 mm²115 A74.21 V (618.42%)0.0 V122.41 V (1020.1%)31539.3 WDrop/Amp High
1 AWG42.41 mm²130 A58.83 V (490.24%)0.0 V97.04 V (808.67%)25002.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A46.64 V (388.69%)0.0 V76.94 V (641.16%)19823.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A37.0 V (308.34%)0.0 V61.03 V (508.61%)15725.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.35 V (244.57%)0.0 V48.41 V (403.43%)12473.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.27 V (193.95%)0.0 V38.39 V (319.92%)9891.3 WDrop/Amp High
250 kcmil126.7 mm²255 A19.69 V (164.1%)0.0 V32.48 V (270.68%)8369.0 WDrop/Amp High
300 kcmil152.0 mm²285 A16.41 V (136.78%)0.0 V27.08 V (225.63%)6976.0 WDrop/Amp High
350 kcmil177.3 mm²310 A14.07 V (117.27%)0.0 V23.21 V (193.43%)5980.5 WDrop/Amp High
400 kcmil202.7 mm²335 A12.31 V (102.57%)0.0 V20.3 V (169.19%)5231.1 WDrop/Amp High
500 kcmil253.4 mm²380 A9.85 V (82.05%)2.2 V16.24 V (135.34%)4184.5 WDrop/Amp High
600 kcmil304.0 mm²420 A8.21 V (68.39%)3.8 V13.54 V (112.81%)3488.0 WDrop/Amp High
750 kcmil380.0 mm²475 A6.57 V (54.71%)5.4 V10.83 V (90.25%)2790.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.92 V (41.03%)7.1 V8.12 V (67.68%)2092.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 450 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 450 feet one-way at 12V (DC), you need 14× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.93%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.12V (67.68%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.