🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 500 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)16× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.85%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.02V (75.2%)
Voltage at Load End11.7 VLoss: 0.34 V (145.3 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 500 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1332.77 V (11106.39%)0.0 V2198.44 V (18320.36%)566426.1 WDrop/Amp High
12 AWG3.31 mm²20 A837.51 V (6979.24%)0.0 V1381.5 V (11512.49%)355941.5 WDrop/Amp High
10 AWG5.26 mm²30 A527.03 V (4391.88%)0.0 V869.35 V (7244.55%)223986.0 WDrop/Amp High
8 AWG8.37 mm²50 A331.2 V (2760.01%)0.0 V546.33 V (4552.73%)140760.6 WDrop/Amp High
6 AWG13.3 mm²65 A208.43 V (1736.94%)0.0 V343.82 V (2865.14%)88583.9 WDrop/Amp High
4 AWG21.15 mm²85 A131.07 V (1092.26%)0.0 V216.21 V (1801.72%)55705.3 WDrop/Amp High
3 AWG26.67 mm²100 A103.94 V (866.19%)0.0 V171.46 V (1428.81%)44175.7 WDrop/Amp High
2 AWG33.62 mm²115 A82.46 V (687.13%)0.0 V136.01 V (1133.44%)35043.6 WDrop/Amp High
1 AWG42.41 mm²130 A65.37 V (544.71%)0.0 V107.82 V (898.52%)27780.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A51.83 V (431.88%)0.0 V85.49 V (712.4%)22025.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A41.11 V (342.6%)0.0 V67.81 V (565.12%)17472.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A32.61 V (271.75%)0.0 V53.79 V (448.26%)13859.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A25.86 V (215.5%)0.0 V42.66 V (355.47%)10990.4 WDrop/Amp High
250 kcmil126.7 mm²255 A21.88 V (182.33%)0.0 V36.09 V (300.76%)9298.9 WDrop/Amp High
300 kcmil152.0 mm²285 A18.24 V (151.98%)0.0 V30.08 V (250.7%)7751.1 WDrop/Amp High
350 kcmil177.3 mm²310 A15.64 V (130.29%)0.0 V25.79 V (214.93%)6645.0 WDrop/Amp High
400 kcmil202.7 mm²335 A13.68 V (113.97%)0.0 V22.56 V (187.99%)5812.4 WDrop/Amp High
500 kcmil253.4 mm²380 A10.94 V (91.17%)1.1 V18.05 V (150.38%)4649.4 WDrop/Amp High
600 kcmil304.0 mm²420 A9.12 V (75.99%)2.9 V15.04 V (125.35%)3875.5 WDrop/Amp High
750 kcmil380.0 mm²475 A7.3 V (60.79%)4.7 V12.03 V (100.28%)3100.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.47 V (45.59%)6.5 V9.02 V (75.2%)2325.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 500 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 500 feet one-way at 12V (DC), you need 16× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.85%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.02V (75.2%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.