⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 800 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.43%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 14.44V (12.03%)
Voltage at Load End117.1 VLoss: 2.92 V (1240.1 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 800 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2132.43 V (1777.02%)0.0 V3517.51 V (2931.26%)906281.8 WDrop/Amp High
12 AWG3.31 mm²20 A1340.01 V (1116.68%)0.0 V2210.4 V (1842.0%)569506.4 WDrop/Amp High
10 AWG5.26 mm²30 A843.24 V (702.7%)0.0 V1390.95 V (1159.13%)358377.6 WDrop/Amp High
8 AWG8.37 mm²50 A529.92 V (441.6%)0.0 V874.12 V (728.44%)225217.0 WDrop/Amp High
6 AWG13.3 mm²65 A333.49 V (277.91%)0.0 V550.11 V (458.42%)141734.3 WDrop/Amp High
4 AWG21.15 mm²85 A209.71 V (174.76%)0.0 V345.93 V (288.27%)89128.4 WDrop/Amp High
3 AWG26.67 mm²100 A166.31 V (138.59%)0.0 V274.33 V (228.61%)70681.1 WDrop/Amp High
2 AWG33.62 mm²115 A131.93 V (109.94%)0.0 V217.62 V (181.35%)56069.8 WDrop/Amp High
1 AWG42.41 mm²130 A104.58 V (87.15%)15.4 V172.52 V (143.76%)44448.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A82.92 V (69.1%)37.1 V136.78 V (113.98%)35241.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A65.78 V (54.82%)54.2 V108.5 V (90.42%)27955.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A52.18 V (43.48%)67.8 V86.07 V (71.72%)22174.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A41.38 V (34.48%)78.6 V68.25 V (56.88%)17584.6 WDrop/Amp High
250 kcmil126.7 mm²255 A35.01 V (29.17%)85.0 V57.75 V (48.12%)14878.2 WDrop/Amp High
300 kcmil152.0 mm²285 A29.18 V (24.32%)90.8 V48.13 V (40.11%)12401.8 WDrop/Amp High
350 kcmil177.3 mm²310 A25.02 V (20.85%)95.0 V41.27 V (34.39%)10632.1 WDrop/Amp High
400 kcmil202.7 mm²335 A21.88 V (18.23%)98.1 V36.09 V (30.08%)9299.8 WDrop/Amp High
500 kcmil253.4 mm²380 A17.5 V (14.59%)102.5 V28.87 V (24.06%)7439.1 WDrop/Amp High
600 kcmil304.0 mm²420 A14.59 V (12.16%)105.4 V24.07 V (20.06%)6200.9 WDrop/Amp High
750 kcmil380.0 mm²475 A11.67 V (9.73%)108.3 V19.25 V (16.04%)4960.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.75 V (7.29%)111.2 V14.44 V (12.03%)3720.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 800 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 800 feet one-way at 120V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.92V (2.43%) and delivers 117.1V at the load.

What size aluminum wire is required for 425 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 14.44V (12.03%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.