⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 800 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 14.44V (6.02%)
Voltage at Load End235.6 VLoss: 4.38 V (1860.2 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2132.43 V (888.51%)0.0 V3517.51 V (1465.63%)906281.8 WDrop/Amp High
12 AWG3.31 mm²20 A1340.01 V (558.34%)0.0 V2210.4 V (921.0%)569506.4 WDrop/Amp High
10 AWG5.26 mm²30 A843.24 V (351.35%)0.0 V1390.95 V (579.56%)358377.6 WDrop/Amp High
8 AWG8.37 mm²50 A529.92 V (220.8%)0.0 V874.12 V (364.22%)225217.0 WDrop/Amp High
6 AWG13.3 mm²65 A333.49 V (138.96%)0.0 V550.11 V (229.21%)141734.3 WDrop/Amp High
4 AWG21.15 mm²85 A209.71 V (87.38%)30.3 V345.93 V (144.14%)89128.4 WDrop/Amp High
3 AWG26.67 mm²100 A166.31 V (69.3%)73.7 V274.33 V (114.3%)70681.1 WDrop/Amp High
2 AWG33.62 mm²115 A131.93 V (54.97%)108.1 V217.62 V (90.68%)56069.8 WDrop/Amp High
1 AWG42.41 mm²130 A104.58 V (43.58%)135.4 V172.52 V (71.88%)44448.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A82.92 V (34.55%)157.1 V136.78 V (56.99%)35241.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A65.78 V (27.41%)174.2 V108.5 V (45.21%)27955.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A52.18 V (21.74%)187.8 V86.07 V (35.86%)22174.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A41.38 V (17.24%)198.6 V68.25 V (28.44%)17584.6 WDrop/Amp High
250 kcmil126.7 mm²255 A35.01 V (14.59%)205.0 V57.75 V (24.06%)14878.2 WDrop/Amp High
300 kcmil152.0 mm²285 A29.18 V (12.16%)210.8 V48.13 V (20.06%)12401.8 WDrop/Amp High
350 kcmil177.3 mm²310 A25.02 V (10.42%)215.0 V41.27 V (17.19%)10632.1 WDrop/Amp High
400 kcmil202.7 mm²335 A21.88 V (9.12%)218.1 V36.09 V (15.04%)9299.8 WDrop/Amp High
500 kcmil253.4 mm²380 A17.5 V (7.29%)222.5 V28.87 V (12.03%)7439.1 WDrop/Amp High
600 kcmil304.0 mm²420 A14.59 V (6.08%)225.4 V24.07 V (10.03%)6200.9 WDrop/Amp High
750 kcmil380.0 mm²475 A11.67 V (4.86%)228.3 V19.25 V (8.02%)4960.7 W~ ≤5%
1000 kcmil506.7 mm²545 A8.75 V (3.65%)231.2 V14.44 V (6.02%)3720.3 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 800 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.38V (1.82%) and delivers 235.6V at the load.

What size aluminum wire is required for 425 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 14.44V (6.02%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.