🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.58%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 12.5V (5.21%)
Voltage at Load End236.2 VLoss: 3.79 V (2790.2 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1846.74 V (769.47%)0.0 V3046.25 V (1269.27%)1359422.7 WDrop/Amp High
12 AWG3.31 mm²20 A1160.49 V (483.54%)0.0 V1914.26 V (797.61%)854259.6 WDrop/Amp High
10 AWG5.26 mm²30 A730.27 V (304.28%)0.0 V1204.6 V (501.92%)537566.4 WDrop/Amp High
8 AWG8.37 mm²50 A458.93 V (191.22%)0.0 V757.01 V (315.42%)337825.5 WDrop/Amp High
6 AWG13.3 mm²65 A288.81 V (120.34%)0.0 V476.41 V (198.5%)212601.4 WDrop/Amp High
4 AWG21.15 mm²85 A181.62 V (75.67%)58.4 V299.58 V (124.83%)133692.6 WDrop/Amp High
3 AWG26.67 mm²100 A144.03 V (60.01%)96.0 V237.58 V (98.99%)106021.7 WDrop/Amp High
2 AWG33.62 mm²115 A114.25 V (47.61%)125.7 V188.47 V (78.53%)84104.7 WDrop/Amp High
1 AWG42.41 mm²130 A90.57 V (37.74%)149.4 V149.4 V (62.25%)66672.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A71.81 V (29.92%)168.2 V118.46 V (49.36%)52862.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A56.97 V (23.74%)183.0 V93.97 V (39.15%)41933.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A45.19 V (18.83%)194.8 V74.53 V (31.06%)33262.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A35.83 V (14.93%)204.2 V59.11 V (24.63%)26376.9 WDrop/Amp High
250 kcmil126.7 mm²255 A30.32 V (12.63%)209.7 V50.01 V (20.84%)22317.3 WDrop/Amp High
300 kcmil152.0 mm²285 A25.27 V (10.53%)214.7 V41.69 V (17.37%)18602.6 WDrop/Amp High
350 kcmil177.3 mm²310 A21.67 V (9.03%)218.3 V35.74 V (14.89%)15948.1 WDrop/Amp High
400 kcmil202.7 mm²335 A18.95 V (7.9%)221.0 V31.26 V (13.02%)13949.7 WDrop/Amp High
500 kcmil253.4 mm²380 A15.16 V (6.32%)224.8 V25.0 V (10.42%)11158.6 WDrop/Amp High
600 kcmil304.0 mm²420 A12.64 V (5.26%)227.4 V20.84 V (8.68%)9301.3 WDrop/Amp High
750 kcmil380.0 mm²475 A10.11 V (4.21%)229.9 V16.67 V (6.95%)7441.1 W~ ≤5%
1000 kcmil506.7 mm²545 A7.58 V (3.16%)232.4 V12.5 V (5.21%)5580.4 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 800 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.79V (1.58%) and delivers 236.2V at the load.

What size aluminum wire is required for 425 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 12.5V (5.21%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.