45 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.6%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 3.23V (2.69%)
Voltage at Load End116.9 VLoss: 3.11 V (140.2 W)
Power & Breaker (125%)5.4 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A63.5 V (52.92%)56.5 V104.75 V (87.29%)2857.6 WDrop/Amp High
12 AWG3.31 mm²20 A39.9 V (33.25%)80.1 V65.82 V (54.85%)1795.7 WDrop/Amp High
10 AWG5.26 mm²30 A25.11 V (20.93%)94.9 V41.42 V (34.52%)1130.0 WDrop/Amp High
8 AWG8.37 mm²50 A15.78 V (13.15%)104.2 V26.03 V (21.69%)710.1 WDrop/Amp High
6 AWG13.3 mm²65 A9.93 V (8.28%)110.1 V16.38 V (13.65%)446.9 WDrop/Amp High
4 AWG21.15 mm²85 A6.25 V (5.2%)113.8 V10.3 V (8.58%)281.0 WDrop/Amp High
3 AWG26.67 mm²100 A4.95 V (4.13%)115.0 V8.17 V (6.81%)222.9 W~ ≤5%
2 AWG33.62 mm²115 A3.93 V (3.27%)116.1 V6.48 V (5.4%)176.8 W~ ≤5%
1 AWG42.41 mm²130 A3.11 V (2.6%)116.9 V5.14 V (4.28%)140.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.47 V (2.06%)117.5 V4.07 V (3.39%)111.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.96 V (1.63%)118.0 V3.23 V (2.69%)88.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.55 V (1.29%)118.4 V2.56 V (2.14%)69.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.23 V (1.03%)118.8 V2.03 V (1.69%)55.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.04 V (0.87%)119.0 V1.72 V (1.43%)46.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.87 V (0.72%)119.1 V1.43 V (1.19%)39.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.74 V (0.62%)119.3 V1.23 V (1.02%)33.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.65 V (0.54%)119.3 V1.07 V (0.9%)29.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.52 V (0.43%)119.5 V0.86 V (0.72%)23.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.43 V (0.36%)119.6 V0.72 V (0.6%)19.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.35 V (0.29%)119.7 V0.57 V (0.48%)15.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.26 V (0.22%)119.7 V0.43 V (0.36%)11.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 225 feet one-way at 120V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 3.11V (2.6%) and delivers 116.9V at the load.

What size aluminum wire is required for 45 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 3.23V (2.69%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.