🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.52%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 12.54V (2.61%)
Voltage at Load End467.9 VLoss: 12.1 V (942.9 W)
Power & Breaker (125%)37.41 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A195.54 V (40.74%)284.5 V322.54 V (67.2%)15240.6 WDrop/Amp High
12 AWG3.31 mm²20 A122.88 V (25.6%)357.1 V202.69 V (42.23%)9577.2 WDrop/Amp High
10 AWG5.26 mm²30 A77.32 V (16.11%)402.7 V127.55 V (26.57%)6026.7 WDrop/Amp High
8 AWG8.37 mm²50 A48.59 V (10.12%)431.4 V80.15 V (16.7%)3787.4 WDrop/Amp High
6 AWG13.3 mm²65 A30.58 V (6.37%)449.4 V50.44 V (10.51%)2383.5 WDrop/Amp High
4 AWG21.15 mm²85 A19.23 V (4.01%)460.8 V31.72 V (6.61%)1498.8 W~ ≤5%
3 AWG26.67 mm²100 A15.25 V (3.18%)464.8 V25.16 V (5.24%)1188.6 W~ ≤5%
2 AWG33.62 mm²115 A12.1 V (2.52%)467.9 V19.96 V (4.16%)942.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A9.59 V (2.0%)470.4 V15.82 V (3.3%)747.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A7.6 V (1.58%)472.4 V12.54 V (2.61%)592.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A6.03 V (1.26%)474.0 V9.95 V (2.07%)470.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.78 V (1.0%)475.2 V7.89 V (1.64%)372.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.79 V (0.79%)476.2 V6.26 V (1.3%)295.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.21 V (0.67%)476.8 V5.3 V (1.1%)250.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.68 V (0.56%)477.3 V4.41 V (0.92%)208.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.29 V (0.48%)477.7 V3.78 V (0.79%)178.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.01 V (0.42%)478.0 V3.31 V (0.69%)156.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.61 V (0.33%)478.4 V2.65 V (0.55%)125.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.34 V (0.28%)478.7 V2.21 V (0.46%)104.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.07 V (0.22%)478.9 V1.77 V (0.37%)83.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.8 V (0.17%)479.2 V1.32 V (0.28%)62.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 800 feet one-way at 480V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 12.1V (2.52%) and delivers 467.9V at the load.

What size aluminum wire is required for 45 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 12.54V (2.61%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.