⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.96%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.59V (3.16%)
Voltage at Load End237.7 VLoss: 2.3 V (2986.9 W)
Power & Breaker (125%)311.77 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1120.26 V (466.78%)0.0 V1847.91 V (769.96%)1455264.3 WDrop/Amp High
12 AWG3.31 mm²20 A703.97 V (293.32%)0.0 V1161.22 V (483.84%)914486.3 WDrop/Amp High
10 AWG5.26 mm²30 A442.99 V (184.58%)0.0 V730.73 V (304.47%)575465.7 WDrop/Amp High
8 AWG8.37 mm²50 A278.39 V (116.0%)0.0 V459.22 V (191.34%)361642.7 WDrop/Amp High
6 AWG13.3 mm²65 A175.2 V (73.0%)64.8 V289.0 V (120.42%)227590.2 WDrop/Amp High
4 AWG21.15 mm²85 A110.17 V (45.91%)129.8 V181.73 V (75.72%)143118.2 WDrop/Amp High
3 AWG26.67 mm²100 A87.37 V (36.4%)152.6 V144.12 V (60.05%)113496.4 WDrop/Amp High
2 AWG33.62 mm²115 A69.31 V (28.88%)170.7 V114.33 V (47.64%)90034.2 WDrop/Amp High
1 AWG42.41 mm²130 A54.94 V (22.89%)185.1 V90.63 V (37.76%)71373.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A43.56 V (18.15%)196.4 V71.86 V (29.94%)56589.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A34.56 V (14.4%)205.4 V57.0 V (23.75%)44890.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A27.41 V (11.42%)212.6 V45.21 V (18.84%)35607.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A21.74 V (9.06%)218.3 V35.85 V (14.94%)28236.5 WDrop/Amp High
250 kcmil126.7 mm²255 A18.39 V (7.66%)221.6 V30.34 V (12.64%)23890.7 WDrop/Amp High
300 kcmil152.0 mm²285 A15.33 V (6.39%)224.7 V25.29 V (10.54%)19914.1 WDrop/Amp High
350 kcmil177.3 mm²310 A13.14 V (5.48%)226.9 V21.68 V (9.03%)17072.5 WDrop/Amp High
400 kcmil202.7 mm²335 A11.5 V (4.79%)228.5 V18.96 V (7.9%)14933.2 WDrop/Amp High
500 kcmil253.4 mm²380 A9.2 V (3.83%)230.8 V15.17 V (6.32%)11945.3 WDrop/Amp High
600 kcmil304.0 mm²420 A7.66 V (3.19%)232.3 V12.64 V (5.27%)9957.1 WDrop/Amp High
750 kcmil380.0 mm²475 A6.13 V (2.55%)233.9 V10.11 V (4.21%)7965.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.6 V (1.92%)235.4 V7.59 V (3.16%)5973.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 275 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.3V (0.96%) and delivers 237.7V at the load.

What size aluminum wire is required for 750 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.59V (3.16%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.