225 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 275 ft (83.8 m) one-way run.
Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.65%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 5.69V (2.73%)
Voltage at Load End202.5 VLoss: 5.52 V (2150.2 W)
Power & Breaker (125%)81.06 kW300A Breaker Recommended
All AWG & kcmil Wire Gauges for 225 Amps at 275 Feet (208V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 336.08 V (161.58%) | 0.0 V | 554.37 V (266.53%) | 130973.8 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 211.19 V (101.53%) | 0.0 V | 348.37 V (167.48%) | 82303.8 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 132.9 V (63.89%) | 75.1 V | 219.22 V (105.39%) | 51791.9 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 83.52 V (40.15%) | 124.5 V | 137.77 V (66.23%) | 32547.8 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 52.56 V (25.27%) | 155.4 V | 86.7 V (41.68%) | 20483.1 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 33.05 V (15.89%) | 174.9 V | 54.52 V (26.21%) | 12880.6 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 26.21 V (12.6%) | 181.8 V | 43.24 V (20.79%) | 10214.7 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 20.79 V (10.0%) | 187.2 V | 34.3 V (16.49%) | 8103.1 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 16.48 V (7.92%) | 191.5 V | 27.19 V (13.07%) | 6423.6 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 13.07 V (6.28%) | 194.9 V | 21.56 V (10.36%) | 5093.0 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 10.37 V (4.98%) | 197.6 V | 17.1 V (8.22%) | 4040.1 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 8.22 V (3.95%) | 199.8 V | 13.56 V (6.52%) | 3204.6 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 6.52 V (3.14%) | 201.5 V | 10.76 V (5.17%) | 2541.3 W | ~ ≤5% |
| 250 kcmil | 126.7 mm² | 255 A | 5.52 V (2.65%) | 202.5 V | 9.1 V (4.38%) | 2150.2 W | ✓ PASS (≤3%) |
| 300 kcmil | 152.0 mm² | 285 A | 4.6 V (2.21%) | 203.4 V | 7.59 V (3.65%) | 1792.3 W | ✓ PASS (≤3%) |
| 350 kcmil | 177.3 mm² | 310 A | 3.94 V (1.9%) | 204.1 V | 6.5 V (3.13%) | 1536.5 W | ✓ PASS (≤3%) |
| 400 kcmil | 202.7 mm² | 335 A | 3.45 V (1.66%) | 204.6 V | 5.69 V (2.73%) | 1344.0 W | ✓ PASS (≤3%) |
| 500 kcmil | 253.4 mm² | 380 A | 2.76 V (1.33%) | 205.2 V | 4.55 V (2.19%) | 1075.1 W | ✓ PASS (≤3%) |
| 600 kcmil | 304.0 mm² | 420 A | 2.3 V (1.11%) | 205.7 V | 3.79 V (1.82%) | 896.1 W | ✓ PASS (≤3%) |
| 750 kcmil | 380.0 mm² | 475 A | 1.84 V (0.88%) | 206.2 V | 3.03 V (1.46%) | 716.9 W | ✓ PASS (≤3%) |
| 1000 kcmil | 506.7 mm² | 545 A | 1.38 V (0.66%) | 206.6 V | 2.28 V (1.09%) | 537.6 W | ✓ PASS (≤3%) |
Frequently Asked Engineering Questions
What size copper wire do I need for 225 amps at 275 feet (208V)?
To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 275 feet one-way at 208V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 5.52V (2.65%) and delivers 202.5V at the load.
What size aluminum wire is required for 225 amps at 275 feet?
Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 5.69V (2.73%).
What breaker size is needed for a 225A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.
Compare Other Distances & Amperages
225 Amp Wire Size by Distance (208V)