🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 6.32V (2.63%)
Voltage at Load End233.9 VLoss: 6.13 V (2654.5 W)
Power & Breaker (125%)103.92 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A373.42 V (155.59%)0.0 V615.97 V (256.65%)161696.0 WDrop/Amp High
12 AWG3.31 mm²20 A234.66 V (97.77%)5.3 V387.07 V (161.28%)101609.6 WDrop/Amp High
10 AWG5.26 mm²30 A147.66 V (61.53%)92.3 V243.58 V (101.49%)63940.6 WDrop/Amp High
8 AWG8.37 mm²50 A92.8 V (38.67%)147.2 V153.07 V (63.78%)40182.5 WDrop/Amp High
6 AWG13.3 mm²65 A58.4 V (24.33%)181.6 V96.33 V (40.14%)25287.8 WDrop/Amp High
4 AWG21.15 mm²85 A36.72 V (15.3%)203.3 V60.58 V (25.24%)15902.0 WDrop/Amp High
3 AWG26.67 mm²100 A29.12 V (12.13%)210.9 V48.04 V (20.02%)12610.7 WDrop/Amp High
2 AWG33.62 mm²115 A23.1 V (9.63%)216.9 V38.11 V (15.88%)10003.8 WDrop/Amp High
1 AWG42.41 mm²130 A18.31 V (7.63%)221.7 V30.21 V (12.59%)7930.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.52 V (6.05%)225.5 V23.95 V (9.98%)6287.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.52 V (4.8%)228.5 V19.0 V (7.92%)4987.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.14 V (3.81%)230.9 V15.07 V (6.28%)3956.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.25 V (3.02%)232.8 V11.95 V (4.98%)3137.4 WDrop/Amp High
250 kcmil126.7 mm²255 A6.13 V (2.55%)233.9 V10.11 V (4.21%)2654.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A5.11 V (2.13%)234.9 V8.43 V (3.51%)2212.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.38 V (1.83%)235.6 V7.23 V (3.01%)1896.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.83 V (1.6%)236.2 V6.32 V (2.63%)1659.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.07 V (1.28%)236.9 V5.06 V (2.11%)1327.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.55 V (1.06%)237.4 V4.21 V (1.76%)1106.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.04 V (0.85%)238.0 V3.37 V (1.4%)885.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.53 V (0.64%)238.5 V2.53 V (1.05%)663.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 275 feet one-way at 240V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 6.13V (2.55%) and delivers 233.9V at the load.

What size aluminum wire is required for 250 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 6.32V (2.63%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.