🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.47%
Aluminum Wire (≤3% Drop)2 AWGDrop: 6.16V (2.57%)
Voltage at Load End234.1 VLoss: 5.94 V (207.8 W)
Power & Breaker (125%)8.4 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A60.37 V (25.15%)179.6 V99.58 V (41.49%)2112.8 WDrop/Amp High
12 AWG3.31 mm²20 A37.93 V (15.81%)202.1 V62.57 V (26.07%)1327.7 WDrop/Amp High
10 AWG5.26 mm²30 A23.87 V (9.95%)216.1 V39.38 V (16.41%)835.5 WDrop/Amp High
8 AWG8.37 mm²50 A15.0 V (6.25%)225.0 V24.75 V (10.31%)525.1 WDrop/Amp High
6 AWG13.3 mm²65 A9.44 V (3.93%)230.6 V15.57 V (6.49%)330.4 W~ ≤5%
4 AWG21.15 mm²85 A5.94 V (2.47%)234.1 V9.79 V (4.08%)207.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.71 V (1.96%)235.3 V7.77 V (3.24%)164.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.73 V (1.56%)236.3 V6.16 V (2.57%)130.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.96 V (1.23%)237.0 V4.88 V (2.03%)103.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.35 V (0.98%)237.7 V3.87 V (1.61%)82.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.86 V (0.78%)238.1 V3.07 V (1.28%)65.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.48 V (0.62%)238.5 V2.44 V (1.02%)51.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.17 V (0.49%)238.8 V1.93 V (0.81%)41.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.99 V (0.41%)239.0 V1.63 V (0.68%)34.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.83 V (0.34%)239.2 V1.36 V (0.57%)28.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.71 V (0.3%)239.3 V1.17 V (0.49%)24.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.62 V (0.26%)239.4 V1.02 V (0.43%)21.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.5 V (0.21%)239.5 V0.82 V (0.34%)17.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.41 V (0.17%)239.6 V0.68 V (0.28%)14.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.33 V (0.14%)239.7 V0.55 V (0.23%)11.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.25 V (0.1%)239.8 V0.41 V (0.17%)8.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 275 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 5.94V (2.47%) and delivers 234.1V at the load.

What size aluminum wire is required for 35 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 6.16V (2.57%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.