🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.73%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.83V (9.02%)
Voltage at Load End116.7 VLoss: 3.29 V (1395.1 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1599.32 V (1332.77%)0.0 V2638.13 V (2198.44%)679711.3 WDrop/Amp High
12 AWG3.31 mm²20 A1005.01 V (837.51%)0.0 V1657.8 V (1381.5%)427129.8 WDrop/Amp High
10 AWG5.26 mm²30 A632.43 V (527.03%)0.0 V1043.22 V (869.35%)268783.2 WDrop/Amp High
8 AWG8.37 mm²50 A397.44 V (331.2%)0.0 V655.59 V (546.33%)168912.7 WDrop/Amp High
6 AWG13.3 mm²65 A250.12 V (208.43%)0.0 V412.58 V (343.82%)106300.7 WDrop/Amp High
4 AWG21.15 mm²85 A157.29 V (131.07%)0.0 V259.45 V (216.21%)66846.3 WDrop/Amp High
3 AWG26.67 mm²100 A124.73 V (103.94%)0.0 V205.75 V (171.46%)53010.9 WDrop/Amp High
2 AWG33.62 mm²115 A98.95 V (82.46%)21.1 V163.22 V (136.01%)42052.3 WDrop/Amp High
1 AWG42.41 mm²130 A78.44 V (65.37%)41.6 V129.39 V (107.82%)33336.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A62.19 V (51.83%)57.8 V102.59 V (85.49%)26431.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A49.33 V (41.11%)70.7 V81.38 V (67.81%)20966.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A39.13 V (32.61%)80.9 V64.55 V (53.79%)16631.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A31.03 V (25.86%)89.0 V51.19 V (42.66%)13188.4 WDrop/Amp High
250 kcmil126.7 mm²255 A26.26 V (21.88%)93.7 V43.31 V (36.09%)11158.6 WDrop/Amp High
300 kcmil152.0 mm²285 A21.89 V (18.24%)98.1 V36.1 V (30.08%)9301.3 WDrop/Amp High
350 kcmil177.3 mm²310 A18.76 V (15.64%)101.2 V30.95 V (25.79%)7974.1 WDrop/Amp High
400 kcmil202.7 mm²335 A16.41 V (13.68%)103.6 V27.07 V (22.56%)6974.8 WDrop/Amp High
500 kcmil253.4 mm²380 A13.13 V (10.94%)106.9 V21.65 V (18.05%)5579.3 WDrop/Amp High
600 kcmil304.0 mm²420 A10.94 V (9.12%)109.1 V18.05 V (15.04%)4650.7 WDrop/Amp High
750 kcmil380.0 mm²475 A8.75 V (7.3%)111.2 V14.44 V (12.03%)3720.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.57 V (5.47%)113.4 V10.83 V (9.02%)2790.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 600 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.29V (2.73%) and delivers 116.7V at the load.

What size aluminum wire is required for 425 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.83V (9.02%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.