🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.77%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.07V (2.53%)
Voltage at Load End238.2 VLoss: 1.84 V (1911.7 W)
Power & Breaker (125%)249.42 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A896.21 V (373.42%)0.0 V1478.33 V (615.97%)931369.2 WDrop/Amp High
12 AWG3.31 mm²20 A563.18 V (234.66%)0.0 V928.98 V (387.07%)585271.3 WDrop/Amp High
10 AWG5.26 mm²30 A354.39 V (147.66%)0.0 V584.59 V (243.58%)368298.1 WDrop/Amp High
8 AWG8.37 mm²50 A222.71 V (92.8%)17.3 V367.37 V (153.07%)231451.4 WDrop/Amp High
6 AWG13.3 mm²65 A140.16 V (58.4%)99.8 V231.2 V (96.33%)145657.7 WDrop/Amp High
4 AWG21.15 mm²85 A88.14 V (36.72%)151.9 V145.39 V (60.58%)91595.6 WDrop/Amp High
3 AWG26.67 mm²100 A69.9 V (29.12%)170.1 V115.3 V (48.04%)72637.7 WDrop/Amp High
2 AWG33.62 mm²115 A55.45 V (23.1%)184.6 V91.46 V (38.11%)57621.9 WDrop/Amp High
1 AWG42.41 mm²130 A43.95 V (18.31%)196.0 V72.5 V (30.21%)45679.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A34.85 V (14.52%)205.2 V57.49 V (23.95%)36217.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A27.65 V (11.52%)212.4 V45.6 V (19.0%)28729.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A21.93 V (9.14%)218.1 V36.17 V (15.07%)22788.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.39 V (7.25%)222.6 V28.68 V (11.95%)18071.3 WDrop/Amp High
250 kcmil126.7 mm²255 A14.71 V (6.13%)225.3 V24.27 V (10.11%)15290.0 WDrop/Amp High
300 kcmil152.0 mm²285 A12.26 V (5.11%)227.7 V20.23 V (8.43%)12745.1 WDrop/Amp High
350 kcmil177.3 mm²310 A10.51 V (4.38%)229.5 V17.34 V (7.23%)10926.4 WDrop/Amp High
400 kcmil202.7 mm²335 A9.2 V (3.83%)230.8 V15.17 V (6.32%)9557.2 WDrop/Amp High
500 kcmil253.4 mm²380 A7.36 V (3.07%)232.6 V12.13 V (5.06%)7645.0 WDrop/Amp High
600 kcmil304.0 mm²420 A6.13 V (2.55%)233.9 V10.11 V (4.21%)6372.5 WDrop/Amp High
750 kcmil380.0 mm²475 A4.91 V (2.04%)235.1 V8.09 V (3.37%)5098.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.68 V (1.53%)236.3 V6.07 V (2.53%)3823.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 275 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.84V (0.77%) and delivers 238.2V at the load.

What size aluminum wire is required for 600 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.07V (2.53%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.