⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 5.26V (2.53%)
Voltage at Load End202.9 VLoss: 5.07 V (965.6 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A164.31 V (78.99%)43.7 V271.03 V (130.3%)31304.4 WDrop/Amp High
12 AWG3.31 mm²20 A103.25 V (49.64%)104.8 V170.31 V (81.88%)19671.6 WDrop/Amp High
10 AWG5.26 mm²30 A64.97 V (31.24%)143.0 V107.17 V (51.53%)12378.9 WDrop/Amp High
8 AWG8.37 mm²50 A40.83 V (19.63%)167.2 V67.35 V (32.38%)7779.3 WDrop/Amp High
6 AWG13.3 mm²65 A25.7 V (12.35%)182.3 V42.39 V (20.38%)4895.7 WDrop/Amp High
4 AWG21.15 mm²85 A16.16 V (7.77%)191.8 V26.65 V (12.81%)3078.6 WDrop/Amp High
3 AWG26.67 mm²100 A12.81 V (6.16%)195.2 V21.14 V (10.16%)2441.4 WDrop/Amp High
2 AWG33.62 mm²115 A10.17 V (4.89%)197.8 V16.77 V (8.06%)1936.7 W~ ≤5%
1 AWG42.41 mm²130 A8.06 V (3.87%)199.9 V13.29 V (6.39%)1535.3 W~ ≤5%
1/0 AWG53.49 mm²150 A6.39 V (3.07%)201.6 V10.54 V (5.07%)1217.3 W~ ≤5%
2/0 AWG67.43 mm²175 A5.07 V (2.44%)202.9 V8.36 V (4.02%)965.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.02 V (1.93%)204.0 V6.63 V (3.19%)765.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.19 V (1.53%)204.8 V5.26 V (2.53%)607.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.7 V (1.3%)205.3 V4.45 V (2.14%)513.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.25 V (1.08%)205.8 V3.71 V (1.78%)428.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.93 V (0.93%)206.1 V3.18 V (1.53%)367.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.69 V (0.81%)206.3 V2.78 V (1.34%)321.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.35 V (0.65%)206.7 V2.22 V (1.07%)257.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.12 V (0.54%)206.9 V1.85 V (0.89%)214.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.9 V (0.43%)207.1 V1.48 V (0.71%)171.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.67 V (0.32%)207.3 V1.11 V (0.53%)128.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 275 feet one-way at 208V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 5.07V (2.44%) and delivers 202.9V at the load.

What size aluminum wire is required for 110 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 5.26V (2.53%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.