425 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.67%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.3V (2.07%)
Voltage at Load End204.5 VLoss: 3.47 V (2557.9 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A634.82 V (305.2%)0.0 V1047.15 V (503.44%)467301.5 WDrop/Amp High
12 AWG3.31 mm²20 A398.92 V (191.79%)0.0 V658.03 V (316.36%)293651.7 WDrop/Amp High
10 AWG5.26 mm²30 A251.03 V (120.69%)0.0 V414.08 V (199.08%)184788.4 WDrop/Amp High
8 AWG8.37 mm²50 A157.76 V (75.84%)50.2 V260.22 V (125.11%)116127.5 WDrop/Amp High
6 AWG13.3 mm²65 A99.28 V (47.73%)108.7 V163.76 V (78.73%)73081.7 WDrop/Amp High
4 AWG21.15 mm²85 A62.43 V (30.01%)145.6 V102.98 V (49.51%)45956.8 WDrop/Amp High
3 AWG26.67 mm²100 A49.51 V (23.8%)158.5 V81.67 V (39.26%)36445.0 WDrop/Amp High
2 AWG33.62 mm²115 A39.27 V (18.88%)168.7 V64.78 V (31.15%)28911.0 WDrop/Amp High
1 AWG42.41 mm²130 A31.13 V (14.97%)176.9 V51.36 V (24.69%)22918.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A24.69 V (11.87%)183.3 V40.72 V (19.58%)18171.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.58 V (9.41%)188.4 V32.3 V (15.53%)14414.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.53 V (7.47%)192.5 V25.62 V (12.32%)11433.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.32 V (5.92%)195.7 V20.32 V (9.77%)9067.0 WDrop/Amp High
250 kcmil126.7 mm²255 A10.42 V (5.01%)197.6 V17.19 V (8.26%)7671.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.69 V (4.18%)199.3 V14.33 V (6.89%)6394.7 WDrop/Amp High
350 kcmil177.3 mm²310 A7.45 V (3.58%)200.6 V12.28 V (5.91%)5482.2 WDrop/Amp High
400 kcmil202.7 mm²335 A6.51 V (3.13%)201.5 V10.75 V (5.17%)4795.2 WDrop/Amp High
500 kcmil253.4 mm²380 A5.21 V (2.51%)202.8 V8.6 V (4.13%)3835.8 WDrop/Amp High
600 kcmil304.0 mm²420 A4.34 V (2.09%)203.7 V7.16 V (3.44%)3197.3 WDrop/Amp High
750 kcmil380.0 mm²475 A3.47 V (1.67%)204.5 V5.73 V (2.76%)2557.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.61 V (1.25%)205.4 V4.3 V (2.07%)1918.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 275 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.47V (1.67%) and delivers 204.5V at the load.

What size aluminum wire is required for 425 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.3V (2.07%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.