🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 600 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)19× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.88%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.83V (90.25%)
Voltage at Load End11.7 VLoss: 0.35 V (146.9 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 600 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1599.32 V (13327.67%)0.0 V2638.13 V (21984.43%)679711.3 WDrop/Amp High
12 AWG3.31 mm²20 A1005.01 V (8375.09%)0.0 V1657.8 V (13814.99%)427129.8 WDrop/Amp High
10 AWG5.26 mm²30 A632.43 V (5270.26%)0.0 V1043.22 V (8693.46%)268783.2 WDrop/Amp High
8 AWG8.37 mm²50 A397.44 V (3312.01%)0.0 V655.59 V (5463.28%)168912.7 WDrop/Amp High
6 AWG13.3 mm²65 A250.12 V (2084.33%)0.0 V412.58 V (3438.17%)106300.7 WDrop/Amp High
4 AWG21.15 mm²85 A157.29 V (1310.71%)0.0 V259.45 V (2162.06%)66846.3 WDrop/Amp High
3 AWG26.67 mm²100 A124.73 V (1039.43%)0.0 V205.75 V (1714.57%)53010.9 WDrop/Amp High
2 AWG33.62 mm²115 A98.95 V (824.56%)0.0 V163.22 V (1360.13%)42052.3 WDrop/Amp High
1 AWG42.41 mm²130 A78.44 V (653.66%)0.0 V129.39 V (1078.23%)33336.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A62.19 V (518.26%)0.0 V102.59 V (854.88%)26431.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A49.33 V (411.12%)0.0 V81.38 V (678.15%)20966.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A39.13 V (326.1%)0.0 V64.55 V (537.91%)16631.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A31.03 V (258.6%)0.0 V51.19 V (426.56%)13188.4 WDrop/Amp High
250 kcmil126.7 mm²255 A26.26 V (218.8%)0.0 V43.31 V (360.91%)11158.6 WDrop/Amp High
300 kcmil152.0 mm²285 A21.89 V (182.38%)0.0 V36.1 V (300.84%)9301.3 WDrop/Amp High
350 kcmil177.3 mm²310 A18.76 V (156.35%)0.0 V30.95 V (257.91%)7974.1 WDrop/Amp High
400 kcmil202.7 mm²335 A16.41 V (136.76%)0.0 V27.07 V (225.59%)6974.8 WDrop/Amp High
500 kcmil253.4 mm²380 A13.13 V (109.4%)0.0 V21.65 V (180.46%)5579.3 WDrop/Amp High
600 kcmil304.0 mm²420 A10.94 V (91.19%)1.1 V18.05 V (150.42%)4650.7 WDrop/Amp High
750 kcmil380.0 mm²475 A8.75 V (72.95%)3.2 V14.44 V (120.34%)3720.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.57 V (54.71%)5.4 V10.83 V (90.25%)2790.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 600 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 600 feet one-way at 12V (DC), you need 19× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.88%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.83V (90.25%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.