🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.4%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 6.33V (2.64%)
Voltage at Load End234.2 VLoss: 5.75 V (1869.4 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A560.55 V (233.56%)0.0 V924.64 V (385.27%)182177.5 WDrop/Amp High
12 AWG3.31 mm²20 A352.25 V (146.77%)0.0 V581.04 V (242.1%)114480.1 WDrop/Amp High
10 AWG5.26 mm²30 A221.66 V (92.36%)18.3 V365.64 V (152.35%)72039.8 WDrop/Amp High
8 AWG8.37 mm²50 A139.3 V (58.04%)100.7 V229.78 V (95.74%)45272.3 WDrop/Amp High
6 AWG13.3 mm²65 A87.66 V (36.53%)152.3 V144.61 V (60.25%)28490.9 WDrop/Amp High
4 AWG21.15 mm²85 A55.13 V (22.97%)184.9 V90.93 V (37.89%)17916.3 WDrop/Amp High
3 AWG26.67 mm²100 A43.72 V (18.22%)196.3 V72.11 V (30.05%)14208.1 WDrop/Amp High
2 AWG33.62 mm²115 A34.68 V (14.45%)205.3 V57.21 V (23.84%)11270.9 WDrop/Amp High
1 AWG42.41 mm²130 A27.49 V (11.46%)212.5 V45.35 V (18.9%)8934.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.8 V (9.08%)218.2 V35.96 V (14.98%)7084.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.29 V (7.2%)222.7 V28.52 V (11.88%)5619.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.72 V (5.71%)226.3 V22.62 V (9.43%)4457.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.88 V (4.53%)229.1 V17.94 V (7.48%)3534.8 WDrop/Amp High
250 kcmil126.7 mm²255 A9.2 V (3.83%)230.8 V15.18 V (6.32%)2990.8 WDrop/Amp High
300 kcmil152.0 mm²285 A7.67 V (3.2%)232.3 V12.65 V (5.27%)2493.0 WDrop/Amp High
350 kcmil177.3 mm²310 A6.58 V (2.74%)233.4 V10.85 V (4.52%)2137.2 WDrop/Amp High
400 kcmil202.7 mm²335 A5.75 V (2.4%)234.2 V9.49 V (3.95%)1869.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.6 V (1.92%)235.4 V7.59 V (3.16%)1495.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.84 V (1.6%)236.2 V6.33 V (2.64%)1246.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.07 V (1.28%)236.9 V5.06 V (2.11%)997.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.3 V (0.96%)237.7 V3.8 V (1.58%)747.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 275 feet one-way at 240V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 5.75V (2.4%) and delivers 234.2V at the load.

What size aluminum wire is required for 325 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 6.33V (2.64%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.