⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.74%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.06V (3.38%)
Voltage at Load End116.7 VLoss: 3.28 V (1395.2 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A599.75 V (499.79%)0.0 V989.3 V (824.42%)254891.7 WDrop/Amp High
12 AWG3.31 mm²20 A376.88 V (314.07%)0.0 V621.67 V (518.06%)160173.7 WDrop/Amp High
10 AWG5.26 mm²30 A237.16 V (197.63%)0.0 V391.21 V (326.0%)100793.7 WDrop/Amp High
8 AWG8.37 mm²50 A149.04 V (124.2%)0.0 V245.85 V (204.87%)63342.3 WDrop/Amp High
6 AWG13.3 mm²65 A93.79 V (78.16%)26.2 V154.72 V (128.93%)39862.8 WDrop/Amp High
4 AWG21.15 mm²85 A58.98 V (49.15%)61.0 V97.29 V (81.08%)25067.4 WDrop/Amp High
3 AWG26.67 mm²100 A46.77 V (38.98%)73.2 V77.16 V (64.3%)19879.1 WDrop/Amp High
2 AWG33.62 mm²115 A37.11 V (30.92%)82.9 V61.21 V (51.0%)15769.6 WDrop/Amp High
1 AWG42.41 mm²130 A29.41 V (24.51%)90.6 V48.52 V (40.43%)12501.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A23.32 V (19.43%)96.7 V38.47 V (32.06%)9911.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.5 V (15.42%)101.5 V30.52 V (25.43%)7862.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.67 V (12.23%)105.3 V24.21 V (20.17%)6236.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.64 V (9.7%)108.4 V19.2 V (16.0%)4945.7 WDrop/Amp High
250 kcmil126.7 mm²255 A9.85 V (8.2%)110.2 V16.24 V (13.53%)4184.5 WDrop/Amp High
300 kcmil152.0 mm²285 A8.21 V (6.84%)111.8 V13.54 V (11.28%)3488.0 WDrop/Amp High
350 kcmil177.3 mm²310 A7.04 V (5.86%)113.0 V11.61 V (9.67%)2990.3 WDrop/Amp High
400 kcmil202.7 mm²335 A6.15 V (5.13%)113.8 V10.15 V (8.46%)2615.6 WDrop/Amp High
500 kcmil253.4 mm²380 A4.92 V (4.1%)115.1 V8.12 V (6.77%)2092.2 WDrop/Amp High
600 kcmil304.0 mm²420 A4.1 V (3.42%)115.9 V6.77 V (5.64%)1744.0 WDrop/Amp High
750 kcmil380.0 mm²475 A3.28 V (2.74%)116.7 V5.42 V (4.51%)1395.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.46 V (2.05%)117.5 V4.06 V (3.38%)1046.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 225 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.28V (2.74%) and delivers 116.7V at the load.

What size aluminum wire is required for 425 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.06V (3.38%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.